Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 352
7 EtherCAT communication
7.7 Parameterising the counter
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Further information:Product description
( 15)
Parameter data
Process alarm The activation of a process alarm can be parameterised. A process alarm can be triggered in
the case of the following events:
•Open hardware gate
Closed hardware gate
Counter limit overflow
Counter limit underflow
Comparison value reached
Final value reached
•Latch value reached
Diagnosealarm If the diagnostic alarm is enabled in the parameter setting, it occurs if another process alarm
is triggered for the same event during a process alarm processing.
Diagnostic function Diagnostic functions are provided by the modules.
Diagnostic
information
The diagnostic information describes the diagnostic contents that can be read out of a
module. Diagnostic information is not automatically sent by the module but must be read
out actively via SDO access.
Subindex Name Description/value Lenze
01 Diagnostics* A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bit 5 ... 0: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
02 Input frequency
Track A
Filters for instance serve to filter signal peaks in the case of an
unclean input signal.
0 (0x00): 500 kHz
1 (0x01): 300 kHz
2 (0x02): 100 kHz
3 (0x03): 60 kHz
4 (0x04): 30 kHz
6 (0x06): 10 kHz
7 (0x07): 5 kHz
8 (0x08): 2 kHz
9 (0x09): 1 kHz
Other values are not permissible!
0x02
03 Input frequency
Track B
0x02
04 Input frequency
Latch
0x02
05 Input frequency
Gate
0x02
06 Input frequency
Reset
0x00
07 Reserved
08 Alarm response* Setting activates process alarm
Bit 0: Proc. alarm HW gate open
Bit 1: Proc. alarm HW gate closed
Bit 2: Proc. alarm overflow
Bit 3: Proc. alarm underflow
Bit 4: Proc. alarm comparison value
Bit 5: Proc. alarm final value
Bit 6: Proc. alarm latch value
Bit 7: Reserved
0x80