Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 360
7 EtherCAT communication
7.7 Parameterising the counter
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
* The values will only be accepted after the state has changed from "Pre-Operational" to "Operational".
09 Signal evaluation* Bit 2 ... 0: Signal evaluation
• 0b000 = counter deactivated (the other parameter data
details for the counter are ignored)
• 0b001 = rotary transducer 1-fold (connection to "A/pulse"
input)
• 0b010 = rotary transducer 2-fold (connection to "A/pulse"
input)
• 0b011 = rotary transducer 4-fold (connection to "A/pulse"
input and "B/direction")
• 0b100 = direction (pulse at "A/pulse" input and direction at
"B/direction" input)
Bit 6 ... 3: Reserved
Bit 7: Gate function (internal gate)
• 0= abort (counting process starts again from loading value)
• 1 = interrupt (counting process is continued with counter
content)
0x00
0A Final value Upper limitation of the counting range 0x00
0B Start value Lower limitation of the counting range 0x00
0C Hysteresis 0x00
Subindex Name Description/value Lenze