Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 394
7 EtherCAT communication
7.12 Diagnostics
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EPM-S603 - diagnostic alarm
Diagnostic byte Bit 7 ... 0
10 (fixed)
2 Bit 3 ... 0: Module class, 0b1000: function module
Bit 4: channel information available
Bits 7 ... 5: 0 (fixed)
30 (fixed)
40 (fixed)
5 Bit 6 ... 0: Channel type, 0x77: Counter module
Bit 7: More channel types available, 0: no, 1: yes
6 Number of diagnostic bits output by the module per channel (here 0x00))
7 Number of channels of a module (here 0x02)
8 ... 16 0 (fixed)
EPM-S604 - diagnostic alarm
Diagnostic byte Bit 7 ... 0
1 Bit 0: Set in case of module fault
Bit 1: Set in case of internal error
Bit 2: Set in case of external error
Bit 3: Set in case a channel error is active
Bit 4: Set in case the external supply voltage is missing
Bit 6 ... 5: 0 (fix)
Bit 7: Parameterisation error
2 Bit 3 ... 0: Module class, 0b1000: function module
Bit 4: channel information available
Bits 7 ... 5: 0 (fixed)
30 (fixed)
4 Bit 5 ... 0: 0 (fix)
Bit 6: Process alarm lost
Bit 7: 0 (fixed)
5 Bit 6 ... 0: Channel type, 0x77: Counter module
Bit 7: 0 (fixed)
6 Number of diagnostic bits output by the module per channel (here 0x08))
7 Number of channels of a module (here 0x01)
8 Bit 0: Error in channel group 0
9 ... 16 0 (fixed)