9 PROFINET communication
9.11 Parameterising technology modules
551
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter data
Diagnostic data
Since this module does not support alarms, the diagnostic data provides information about this
module.
Data set Name Description/value Lenze
No. Byte
0x80 0 PWM 1: period Set parameters here for the total time for pulse duration and
pulse pause. The time should be selected as a factor for the
20.83 ns basis.
Values below 25 s are ignored. If the pulse duration is
higher or equal to the period, the DO output is set
permanently.
Value range: 1200 ... 8388607 (25 s ... approx. 175 ms)
0x1F40
0x81 0 PWM 2: Period 0x1F40
Diagnostic data record - data record 0x01
Name Byte Function Default
ERR_A 1 Reserved 0x00
MODTYP 1 Module information
Byte 0:
Bit 3 ... 0: Module class (0b1111: Digital module)
Bit 4: channel information available
Bits 7 ... 4: 0 reserved
0x15
ERR_C 1 Reserved 0x00
ERR_D 1 Reserved 0x00
CHTYP 1 Channel type
Byte 0:
Bit 6 ... 0: Channel type (0x72: Digital output)
Bit 7: Reserved
0x72
NUMBIT 1 Number of diagnostic bits per channel
Byte 0: Here 0x00
0x00
NUMCH 1 Number of channels in module
Byte 0: Here 0x02
0x02
CHERR 1 Reserved 0x00
CH0ERR ... CH7ERR 6 Reserved 0x00
DIAG_US 4 Value of s ticker when diagnostics occur
Bytes 0 ...3
0