Table of Functions
175
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
44
29
0h142C
Speed
estimator I
gain2
PM SpdEst
Ki 2
0~32000
30 X X P -
45
29
0h142D
Speed
estimator
feed
forward
high speed
rate [%]
PM Flux
FF %
0~100[%]
30.0 X X P -
46
29
0h142E
Initial pole
position
detection
options
Init Angle
Sel
0 None
1 X
X
P -
1 Angle
2 Align
48
29
0h1430
Current
controller P
gain
ACR P Gain 0-10000
1200 O X I -
49
29
0h1431
Current
controller I
gain
ACR I Gain 0-10000
120 O X O -
50
29
0h1432
Voltage
controller
limit
V Con HR
0~100.0[%]
10.0 X X P -
51
29
0h1433
Voltage
controller I
gain
V Con Ki
0~1000.0[%]
10.0 X X P -
52 0h1434
Torque
controller
output
filter
Torque Out
LPF
0-2000(ms)
0 X X I/P -
53 0h1435
Torque
limit
setting
options
Torque Lmt
Src
0
Keypad-1
0:
Keypad-
1
X X I/P -
1
Keypad-2
2
V1
4
V2
5
I2
6
Int 485
8
FieldBus
9
UserSeqLink
12
Pulse
54
30
0h1436
Positive-
direction
reverse
torque
limit
FWD
+Trq Lmt
0.0-200.0(%)
180 O X I/P -
30
Displayed when DRV-09 is set to 4 (IM Sensorless). This will change the initial value of the
parameter at ADV-74 (Torque limit) to 150%.

Table of Contents