EasyManua.ls Logo

LSIS S100 - Page 188

LSIS S100
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
176
Table of Functions
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
55
30
0h1437
Positive-
direction
regenerati
on
torque
limit
FWD
Trq Lmt
0.0-200.0(%) 180 O X
I/P -
56
30
0h1438
Negative-
direction
regenerati
on
torque
limit
REV +Trq
Lmt
0.0-200.0(%) 180 O X
I/P -
57
30
0h1439
Negative-
direction
reverse
torque
limit
REV Trq
Lmt
0.0-200.0(%) 180 O X
I/P -
62
30
0h143E
Speed limit
setting
Speed Lmt
Src
0
Keypad-1
0:Keypa
d-1
X X I/P -
1
Keypad-2
2
V1
4
V2
5
I2
6
Int 485
7
FieldBus
8
UserSeqLink
63
30
0h143F
Positive-
direction
speed limit
FWD
Speed Lmt
0.00Maximum
frequency [Hz]
60.00 O X I/P -
64
30
0h1440
Negative-
direction
speed limit
REV Speed
Lmt
0.00Maximum
frequency [Hz]
60.00 O X I/P -
65
30
0h1441
Speed
limit
operation
gain
Speed Lmt
Gain
100~5000(%) 500
O X I/P -
69
31
PM speed
search
current
SS Pulse
Curr
15 10~100
O X P
70 0h1446
Speed
search
mode
selection
SS Mode 0
Flying Start-
1
32
0:
Flying
Start-1
X O I/P -
31
Displayed when DRV-09 (Control Mode) is set to 6 (PM Sensorless).
32
Will not be Displayed when DRV-09 is set to 4 (IM Sensorless)