MCS301 - 3ph meter Page 36 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
8.2 Maximum Demand measurement
The demand measurement offers below characteristic:
• Demand measurement type
o support of block demand
o support of sliding demand according DLMS blue book, up to 15 sub-intervals
Demand register Max demand
demand
1 active demand, +P 1-0:1.6.0.255 1-0:1.4.0.255
2 active demand, -P 1-0:2.6.0.255 1-0:2.4.0.255
3 active demand, /+P/ + /-P/ 1-0:15.6.0.255 1-0:15.4.0.255
4 reactive demand, +Q 1-0:3.6.0.255 1-0:3.4.0.255
5 reactive demand, -Q 1-0:4.6.0.255 1-0:4.4.0.255
6 Reactive demand, Q1 *) 1-0:5.6.0.255 1-0:5.5.0.255
7 Reactive demand, Q2 *) 1-0:6.6.0.255 1-0:6.5.0.255
8 Reactive demand, Q3 *) 1-0:7.6.0.255 1-0:7.5.0.255
9 Reactive demand, Q4 *) 1-0:8.6.0.255 1-0:8.5.0.255
10 apparent demand, +S 1-0:9.6.0.255 1-0:9.4.0.255
11 apparent demand, -S 1-0:10.6.0.255 1-0:10.4.0.255
Table 5: list of demand register with OBIS code,
*) available with MCOR FW 1-0:01.01.25
• up to 4 demand tariffs
• up to 15 set of historical data
• resolution on communication interface (6,x) number of decimals: x= 1…3
• resolution on LCD (6,x) number of decimals: x= 1…3
• configurable period, 1..60min (independent from the load profile period)
• power up and power down <= configurable interval
=> Ongoing demand period
• power up and power down >= configurable interval
=> Stop of current demand measurement, restart of new demand period
• time synchronization deviation <= configurable interval
=> Ongoing demand period
• time synchronization deviation >= configurable interval
=> Stop of current demand measurement, restart of new demand period