24 Line loss and transformer loss measurement Page 113 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
24 Line loss and transformer loss measurement
24.1 Line loss (copper loss) measurement
The meter supports the line loss measurement as attached:
The line (cupper) losses I
2
h are stored in separate energy register.
Use of 2 separate register depending on the energy direction
Additional total register independing on the energy direction
Support of historical data (up to 15)
The decimals for the line loss energy register is independently configurable from the
energy register
The cupper loss constant is not stored in the meter. To get the final losses the energy
value of the meter has to be multiplied by the constant “R” entered in the unit Ohm.
24.2 Transformer (iron loss) measurement
The meter supports the transformer loss measurement as attached:
The transformer (iron) losses U
2
h are stored in separate register
Use of 2 separate register depending on the energy direction
Additional total register independing on the energy direction
Support of historical data (up to 15)
The decimals for the transformer loss energy register is independently configurable
from the energy register
The iron loss constant is not stored in the meter. To get the final losses the energy
value of the meter has to be divided by the constant “X” entered in the unit kOhm.