MCS301 - 3ph meter Page 64 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
13.5 Load profile 4 – maximum profile
The load profile 3 should have below characteristic:
• configurable interval, period 3: 1 … 60min
• default interval: 10min
• Max. number of channels: 14
• Max. number of days per channel: 31 (10min, 14 channels)
remark: in case the number of channels is less than 14 the size for the remaining
channels is increased
Maximum Values Profile (7,1-0:99.134.0.255)
channel
Quantity OBIS code
1 Last maximum Value of Voltage L1 1-0:32.26.0.255
2 Last maximum Value of Voltage L2 1-0:52.2260.255
3 Last maximum Value of Voltage L3 1-0:72.26.0.255
4 Last maximum Value of current L1 1-0:31.26.0.255
5 Last maximum Value of current L2 1-0:51.26.0.255
6 Last maximum Value of current L3 1-0:71.26.0.255
7 Last maximum Value of total power factor 1-0:13.26.0.255
8 Last maximum Value of power factor L1 1-0:33.26.0.255
9 Last maximum Value of power factor L2 1-0:53.26.0.255
10 Last maximum Value of power factor L3 1-0:73.26.0.255
11 Last maximum Value of active demand, +P 1-0:1.26.0.255
12 Last maximum Value of active demand, -P 1-0:2.26.0.255
13 Last maximum Value of reactive demand, +Q 1-0:3.26.0.255
14 Last maximum Value of reactive demand, -Q 1-0:4.26.0.255
Table 31: load profile 4 – maximum data