MCS301 - 3ph meter Page 63 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
13.4 Load profile 3 – average profile
The load profile 3 should have below characteristic:
• configurable interval, period 3: 1 … 60min
• default interval: 10min
• Max. number of channels: 14
• Max. number of days per channel: 31 (10min, 14 channels)
remark: in case the number of channels is less than 14 the size for the remaining
channels is increased
Average Values Profile (1-0:99.133.0.255)
channel
Quantity OBIS code
1 Last Average Value of Voltage L1 1-0:32.25.0.255
Last Average Value of Voltage L2
3 Last Average Value of Voltage L3 1-0:72.25.0.255
4 Last Average Value of current L1 1-0:31.25.0.255
5 Last Average Value of current L2 1-0:51.25.0.255
6 Last Average Value of current L3 1-0:71.25.0.255
7 Last Average Value of total power factor 1-0:13.25.0.255
8 Last Average Value of power factor L1 1-0:33.25.0.255
9 Last Average Value of power factor L2 1-0:53.25.0.255
10 Last Average Value of power factor L3 1-0:73.25.0.255
11 Last Average Value of active demand, +P 1-0:1.25.0.255
12 Last Average Value of active demand, -P 1-0:2.25.0.255
13 Last Average Value of reactive demand, +Q 1-0:3.25.0.255
14 Last Average Value of reactive demand, -Q 1-0:4.25.0.255
Table 30: load profile 3 – average data