32 Type key
32.1 Type key for HW version up to V1.3
MCS301 -
_ _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _
Connection Type:
C Transformer rated meter
D direct connected meter
Nominal Voltage and Network Type
A 3 x 100V or 3 x 110 V (3-wire, 2 Systems)
D 3 x 220V or 3 x 230 V (3-wire, 2 Systems)
1 3 x 58/100V or 3 x 63/110 V (4-wire, 3 Systems)
2 3 x 127/220V (4-wire, 3 Systems)
3 3 x 230/400V (4-wire, 3 Systems)
5 3 x 220/380V or 230/400V (4-wire, 3 System)
W 3 x 58/100V...3x 240/415 V (4-wire, 3 Systems)
E 3 x 58/100V...3x 277/480 V (4-wire, 3 Systems)
Nominal Current:
1 1 (2) A
2 5 (6) A
3 5//1 A or 1 (6) A
4 1 (10) A
5 5 (10) A
A 5 (60) A
B 5 (80) A
C 5 (100) A
E 10 (60) A
F 10 (80) A
G 10 (100) A
Frequency:
1 50 Hz
2 60 Hz
Accuracy Class:
2 Active energy, +A class 0.2S (IEC 62053-22)
C +A energy, cl. 0.5S, C (EN 62053-22, EN50470- 3)
B +A energy, class 1, B (EN 62053-21, EN50470-3)
A +A energy, class 2, A (EN 62053-21, EN50470-3)
Measured Quantities:
1 Active energy only
2 Active energy and reactive energy
3 Active, reactive, apparent energy
Memory size:
E Extended
Structure:
M Modular for external communication modules
closed version, no module support
Battery:
Internal battery for buffering real time clock
E Internal and external battery (RWP)
Communication Interface:
O interface only
S optical and RS485 interface
Additional Functions
x # control inputs (0 .. 2)
x # electronic outputs (S0-Standard) (0 .. 2)
x # electronic outputs (230 V, 100 mA) (0 .. 4)
x # bistable relays (I
max
10A) (0 .. 2)
0 0 0 0 2 outputs (S0)
0 0 4 0 4 electronic outputs (230 V)
0 2 0 2 2 electronic outputs (S0) / 2 relays
0 1 0 1 1 electronic output (S0) / 1 relays
2 0 4 0 2 inputs/2 S0 outputs / 4 outputs (230 V)
2 2 4 2 2 input/2 S0 output/4 outputs (230 V)/ 2 relays
0 no auxiliary power supply
1 with auxiliary power supply (48-230V AC/DC)
M Wired M-Bus Master (EN 13757-2)
0 no wired M-Bus
Remark: for the direct connected meter the number of I/0 is limited to
- RS485 interface
- Wired M-Bus interface
- 1x S0 output

Table of Contents