13.6 Load profile 5 – minimum profile
The load profile 3 should have below characteristic:
configurable interval, period 3: 1 … 60min
default interval: 10min
Max. number of channels: 14
Max. number of days per channel: 31 (10min, 14 channels)
remark: in case the number of channels is less than 14 the size for the remaining
channels is increased
Minimum Values Profile (1-0:99.135.0.255)
channel
Quantity OBIS code
1 Last minimum Value of Voltage L1 1-0:32.23.0.255
2 Last minimum Value of Voltage L2 1-0:52.23.0.255
3 Last minimum Value of Voltage L3 1-0:72.23.0.255
4 Last minimum Value of current L1 1-0:31.23.0.255
5 Last minimum Value of current L2 1-0:51.23.0.255
6 Last minimum Value of current L3 1-0:71.23.0.255
7 Last minimum Value of total power factor 1-0:13.23.0.255
8 Last minimum Value of power factor L1 1-0:33.23.0.255
9 Last minimum Value of power factor L2 1-0:53.23.0.255
10 Last minimum Value of power factor L3 1-0:73.23.0.255
11 Last minimum Value of active demand, +P 1-0:1.23.0.255
12 Last minimum Value of active demand, -P 1-0:2.23.0.255
13 Last minimum Value of reactive demand, +Q 1-0:3.23.0.255
14 Last minimum Value of reactive demand, -Q 1-0:4.23.0.255
Table32: load profile 5 – minimum data