13.8 Snapshot profiles of instantaneous PQ and/or energy values
2 additional readout profiles with up to 50 entries for instantaneous values of energy and
power quality are supported by the reading client through the optical port too:
13.8.1 Instantaneous Energy profile
Below data are the default values for the “Energy Instantaneous values readout”
• Clock 0-0:1.0.0.255
• Device ID1,manufacturing number 0-0:96.1.0.255
• Utility Device ID 1-0:0.0.0.255
• Active import energy, +A , (x=0, 1, 2, 3, 4) 1-0:1.8.x.255
• Active export energy, -A , (x=0, 1, 2, 3, 4) 1-0:2.8.x.255
• Reactive import energy, +R 1-0:3.8.0.255
• Reactive export energy, -R 1-0:4.8.0.255
• Reactive import energy, R1 1-0:5.8.0.255
• Reactive export energy, R2 1-0:6.8.0.255
• Reactive import energy, R3 1-0:7.8.0.255
• Reactive export energy, R4 1-0:8.8.0.255
• Apparent import energy, +S 1-0:9.8.0.255
• Apparent export energy, -S 1-0:10.8.0.255
• Active energy combined, total, /+A/ + /-A, (x=0,1,2,3,4) 1-0:15.8.x.255
• Active energy net, total, /+A/ - /-A, (x=0,1,2,3,4) 1-0:16.8.x.255
• …..
13.8.2 Instantaneous Power Quality profile
Below data are the default values for the “Power Quality Instantaneous readout”
• Clock 0-0:1.0.0.255
• Device ID1,manufacturing number 0-0:96.1.0.255
• Utility Device ID 1-0:0.0.0.255
• Voltage L1, L2, L3 (x=32, 52, 72) 1-0:x.7.0.255
• Current L1, L2, L3 (x=31, 51, 71) 1-0:x.7.0.255
• Power factor L1, L2, L3 (x=33, 53, 73) 1-0:x.7.0.255
• Active import power L1, L2, L3 (x=21, 41, 61) 1-0:x.7.0.255
• Active export power L1, L2, L3 (x=22, 42, 62) 1-0:x.7.0.255
• Reactive import power L1, L2, L3 (x=23, 43, 63) 1-0:x.7.0.255
• Reactive export power L1, L2, L3 (x=24, 44, 64) 1-0:x.7.0.255
• Current (sum over all phases 1-0:90.7.0.255
• Active import power (/+A/ + /-A/ 1-0:15.7.0.255
• Active import power, +A 1-0:1.7.0.255
• Active export power, -A 1-0:2.7.0.255
• Reactive import power, +R 1-0:3.7.0.255
• Reactive export power –R 1-0:4.7.0.255
• Apparent import power, +S 1-0:9.7.0.255
• Apparent import power, -S 1-0:10.7.0.255
• Power factor, +A/+VA 1-0:13.7.0.255
• Phase angle from I(L1) to U(L1) 1-0:81.7.4.255
• Phase angle from I(L2) to U(L2) 1-0:81.7.15.255
• Phase angle from I(L3) to U(L3) 1-0:81.7.26.255
• …..