15.1 Log file 1 – Standard Event Log
Size of the Standard Event Log: 580 entries (rolling storage)
Below events are recorded with time and date stamp in the Standard Event Log
No Name Description
1
Power Down
C
omplete power down of the device.
2
Power Up
D
evice is powered again after a complete power down.
3
Daylight saving time enabled or
disabled
R
egular change from and to daylight saving time. The time stamp shows the time
before the change. This event is not set in case of manual clock changes and in case of
power failures.
4
Clock adjusted (old date/time)
C
lock has been adjusted. The date/time that is stored in the event log is the old
date/time before adjusting the clock.
5
Clock adjusted (new date/time)
C
lock has been adjusted. The date/
time that is stored in the event log is the new
date/time after adjusting the clock.
6
Clock invalid
In
valid
clock, i.e. if the power reserve of the clock has exhausted.
It is set at power up.
7
Replace Battery
B
attery must be exchanged due to the expec
ted end of life time
8
Battery voltage low
C
urrent battery voltage is low.
9
TOU activated
P
assive TOU has been activated.
10
Error register cleared
E
rror register was cleared.
11
Alarm register cleared
A
larm register was cleared.
12
Program memory
error
P
ysical or a logical error in the program memory.
13
RAM error
P
hysical or a logical error in the RAM.
14
NV memory error
P
hysical or a logical error in the non volatile memory
15
Watchdog error
W
atch dog reset or a hardware reset of the microcon
troller.
16
Measurement system error
L
ogical or physical error in the measurement system
17
Firmware ready for activation
N
ew FW has been successfully downloaded and verified
18
Firmware activated
N
ew firmware has been activated
19
Passive TOU program
med
The passive structures of TOU or a new activation date/time were programed
20
External alert detected
Signal detected on the meter's input terminal
21
End of non
-
periodic billing interval
E
nd of a non
-
periodic billing interval
22
Capturing of load
profile 1 enabled
C
apturing of load profile 1 has started
23
Capturing of load profile 1 disabled
C
apturing of load profile 1 has ended
24
Capturing of load profile 2 enabled
C
apturing of load profile 2 has started
25
Capturing of load profile 2 disabl
ed
C
apturing of load profile 2 has ended
47
One/more parameters changed
C
hange of
at least parameter,
with
below
sub
-
events
1 - Demand register 1,2,3,4,7 period
2 - Demand register 1,2,3,4,7 number of period
3 - Limiter Threshold Normal
4 - Limiter Threshold Emergency
5 - LP1 Capture Period
6 - LP2 Capture Period
7 - LP Average Capture Period
8 - LP Max Capture Period
9 - LP Min Capture Period
10 - LP Harmonics Capture Period
11 - Secret change
12 - Security policy changed (meter)
13 - Security policy changed (IHD)
14 – M-Bus security parameters changed
15 - Transformer ratio- current numerator changed
16 - Transformer ratio- voltage numerator changed