17.2 Power outage Counter
There are different power failures considered, to count and store the number of short and long
power failures. The counters and their related COSEM objects are as follow:
Short power outages
Number of Short Power Failures in All Phases (0-0:96.7.0.255);
Number of Short Power Failures in L1 (0-0:96.7.1.255);
Number of Short Power Failures in L2 (0-0:96.7.2.255);
Number of Short Power Failures in L3 (0-0:96.7.3.255);
Number of Short Power Failure in Any Phases (0-0:96.7.21.255);
Long power outages
Number of Long Power Failures in All Phases (0-0:96.7.5.255);
Number of Long Power Failures in Phase L1 (0-0:96.7.6.255);
Number of Long Power Failures in Phase L2 (0-0:96.7.7.255);
Number of Long Power Failures in Phase L3 (0-0:96.7.8.255);
Number of Long Power Failures in Any Phase (0-0:96.7.9.255);
The counter’s value is incremented by “1” in cases of any related event. The counter can’t be
reset. It is reset automatically, if it reaches the maximum value according to its size.
17.3 Power outage duration register
The duration of last long power failure shall be registered by meter. The following registered
store the duration of the last long power failure.
Duration of Last Long Power Failure in All Phases (0-0:96.7.15.255);
Duration of Last Long Power Failure in Phase L1 (0-0:96.7.16.255);
Duration of Last Long Power Failure in Phase L2 (0-0:96.7.17.255);
Duration of Last Long Power Failure in Phase L3 (0-0:96.7.18.255);
Duration of Last Long Power Failure in Any Phase (0-0:96.7.19.255);
17.4 Power Failure Event log for long power outages
There is one event log for power failure as COSEM object “Power Failure Event Log (1-
0:99.97.0.255).
The power failure event log contains all events related to long power outages.
It stores the time stamp, duration of long power failures in any phase (where the time stamp
represents the end of power failure) and event code related to phase (that long power failure
occurred). The more detailed view into the duration of the power outage events is provided via
dedicated COSEM object for each phase. Each entry, recorded in Power Failure Event Log,
contains the following information about power failure events:
Time of power return after long power failure;
Duration of long power failure (in phase L1, L2 and L3);
Event code related to long power failure in L1, L2 and L3;

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Metcom Solutions MCS301 and is the answer not in the manual?

Metcom Solutions MCS301 Specifications

General IconGeneral
BrandMetcom Solutions
ModelMCS301
CategoryMeasuring Instruments
LanguageEnglish