MCS301 - 3ph meter Page 78 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
15.4 Log file 4 – Power Quality Event Log
Size of the Power Quality Event Log: 340 entries (rolling storage)
Below events are recorded with time and date stamp in the Power Quality Event Log
No
Name Description
76 Undervoltage L1 Indicates undervoltage on at least L1 phase was detected.
77 Undervoltage L2 Indicates undervoltage on at least L2 phase was detected.
78 Undervoltage L3 Indicates undervoltage on at least L3 phase was detected.
79 Overvoltage L1 Indicates overvoltage on at least L1 phase was detected.
80 Overvoltage L2 Indicates overvoltage on at least L2 phase was detected.
81 Overvoltage L3 Indicates overvoltage on at least L3 phase was detected.
82 Missing voltage L1 Indicates that voltage of L1 is below the Umin threshold for longer than the time delay.
83 Missing voltage L2 Indicates that voltage of L2 is below the Umin threshold for longer than the time delay.
84
Missing voltage L3
Indicates that
v
oltage o
f L3
is
below the Umin threshold for longer than the time delay.
85
Voltage L1 normal
T
he mains voltage
of L1
is in normal limits again, e.
g. after overvoltage.
86
Voltage L2 normal
T
he mains voltage
of L2
is in normal limits again, e.g. after overvoltage.
87
Voltage L3 normal
T
he mains voltage
of L3
is in normal limits again, e.g. after overvoltage.
90
Phase Asymmetry
Indicates phase asymmetry due to large unbalance of loads connected
92
Bad Voltage Quality L1
Indicates that during one week
, 95 % of the 10
min mean r
.m.s
values of L1
are within
the range of Un+/- 10 % and all 10 mín mean r.m.s. values of L1 shall be within the
range of U
n + 10%/
-
15%.
(acc. EN50160, section 4.2.2)
93
Bad Voltage Quality L2
Same indication as for the voltage L1
94
Bad Voltage Quality L3
Same indication as for the voltage L1
204
Power direction has changed
Indication of power direction change
217
Under
voltage end, phase 1
Amplitude and duration of phase 1, Under voltage end
218
Under voltage end, phase 2
Amplitude and duration of phase 2, Under voltage end
219
Under voltage end, phase 3
Amplitude and duration of phase 3, Under voltage end
220
Over vo
ltage end, phase 1
Amplitude and duration of phase 1, Over voltage end
221
Over voltage end, phase 2
Amplitude and duration of phase 2, Over voltage end
222
Over voltage end, phase 3
Amplitude and duration of phase 3, Over voltage end
223
Missing voltag
e end, phase 1
Amplitude and duration of missing voltage L1
224
Missing voltage end, phase 2
Amplitude and duration of missing voltage L2
225
Missing voltage end, phase 3
Amplitude and duration of missing voltage L3
255
Event log cleared
E
vent log was cleared. This is the first entry in
the effected
event log.
Table 39: Definition of log file 4 – Power Quality Event Log
At the starting of the over/under voltage events (event code 76, 77, 78, 79, 80, 81) the
following parameters are stored in the Power Quality log too
Starting time of the Over/Under voltage
Number of the Over/Under voltage
At the end of the over/under voltage events (event code 217, 218, 219, 220, 221, 222) the
following parameters are stored in the Power Quality log too
End time of the Over/Under voltage
Duration of last Over/Under voltage
Magnitude of the last Over/Under voltage