23 Security functions Page 106 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
23.1.2 Display of alarm register 2
The OBIS code of the alarm register 2 is: 0-0:97.98.1
The bit assignment of the alarm register 2 is shown below
Bit
Alarm Description
0
Power
Down
1
Power
Up
2
Voltage
Missing
Phase
L1
3
Voltage
Missing
Phase
L2
4
Voltage
Missing
Phase
L3
5
Voltage
Normal
Phase
L1
6
Voltage
Normal
Phase
L2
7
Voltage
Normal
Phase
L3
8
Missing
Neutral
9
Phase
Asymmetry
10
Current
Reversal
11
Wrong
Phas
e
Sequence
12
Unexpected
Consumption
13
Key
Exchanged
14
Bad
Voltage
Quality
L1
15
Bad
Voltage
Quality
L2
16
Bad
Voltage
Quality
L3
17
External
Alert
18
Local
Communication
Attempt
19
New
Mbus
Device
Installed
Ch1
20
New
M
-
bus
Device
Installed
Ch2
21
New
M
-
bus
Device
Installed
Ch3
22
New
M
-
bus
Device
Installed
Ch4
23
Reserved
24
Reserved
25
Reserved
26
Reserved
27
M
-
bus
Valve
Alarm
Ch1
28
M
-
bus
Valve
Alarm
Ch2
29
M
-
bus
Valve
Alarm
Ch3
30
M
-
bus
Valve
Alarm
Ch4
31
Disconnect/Reconnect
Fail
ure
Table 166: Alarm Register 2
23.1.3 Display of Fatal Error register
The OBIS code of the error message register is: 0-0:97.97.1
The bit assignment of the Fatal error register is shown below
Bit
Alarm Description
0
Reserved
1
Rese
rved
2
Program
Memory
Error
3
RAM
Error
4
NV
Memory
Error
5
Measurement
System
Error
6
Watchdog
Error
7
Reserved
Table 47: Fatal error messages