19 Inputs / Outputs Page 95 of 142
MCS301 meter - product Manual 1.25 MetCom Solutions GmbH
19.2 Inputs
19.2.1 Control inputs
The meter provides up to 2 control inputs. The assignment of the control input to the
corresponding functions is user-configurable.
Energy tariff control, T1-T2
Maximum demand tariff control, M1-M2
Any Status information
Push activation (only in combination with COM200 / COM300 module)
Electrical characteristics:
- OFF at <= 40V
- ON at >= 60V
Remark: in case of using the 2 control inputs the 2 pulse inputs can’t be used in parallel
19.2.2 Pulse inputs
The meter can provides up to 2 pulse inputs to collect the pulse output of external meters. The
functionality of the pulse inputs described below:
Configurable pulse constant of the inputs
Selection of counting active pulses (import and/or export)
Storing energy and demand data in separate register
Storing pulse input data in a load profile
Possibility to summate the external pulses with the internal register of the meter
Up to 2 summation pulse output
Remark: in case of using the 2 pulse inputs the 2 control inputs can’t be used in parallel