PROTOCOL-SPECIFIC INFORMATION
Table 33: Input Instances 70 and 71 Detail
70
71
0
At
Reference
From
From
Ready
Running2
(REV)
Running1
(FWD)
Warning Faulted
Mapping Detail
Faulted: Inverter fault signal (0=not faulted, 1=faulted). Maps to inverter register 100 (status word), bit
15 (alarm occurrence).
Warning: This bit is not used (it is always 0).
Running1 (FWD): Running forward status signal (0=not running forward, 1=running forward). Maps to
inverter register 100 (status word), bits 0 and 1. The Running1 bit will be 1 whenever bit 0 (inverter
running) and bit 1 (forward rotation) of the status word are both 1, and will be 0 otherwise. Note that if