PROTOCOL-SPECIFIC INFORMATION
123
9
Table 33: Input Instances 70 and 71 Detail
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
Running1
Faulted
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
71
0
At
Reference
Ref
From
Net
Ctrl
From
Net
Ready
Running2
(REV)
Running1
(FWD)
Warning Faulted
1
Drive State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Mapping Detail
Faulted: Inverter fault signal (0=not faulted, 1=faulted). Maps to inverter register 100 (status word), bit
15 (alarm occurrence).
Warning: This bit is not used (it is always 0).
Running1 (FWD): Running forward status signal (0=not running forward, 1=running forward). Maps to
inverter register 100 (status word), bits 0 and 1. The Running1 bit will be 1 whenever bit 0 (inverter
running) and bit 1 (forward rotation) of the status word are both 1, and will be 0 otherwise. Note that if