PROTOCOL-SPECIFIC INFORMATION
the setting of inverter parameter Pr. 190 (RUN terminal function selection) is changed from its factory-
default value, the indicated status of the Running1 bit will no longer be accurate.
Running2 (REV): Running reverse status signal (0=not running reverse, 1=running reverse). Maps to
inverter register 100 (status word), bits 0 and 2. The Running2 bit will be 1 whenever bit 0 (inverter
running) and bit 2 (reverse rotation) of the status word are both 1, and will be 0 otherwise. Note that if
the setting of inverter parameter Pr. 190 (RUN terminal function selection) is changed from its factory-
default value, the indicated status of the Running2 bit will no longer be accurate.
Ready: Inverter ready signal (0=not ready, 1=ready). The Ready bit will be 1 whenever the Drive State
attribute (see below) is in the Ready, Enabled or Stopping state.
CtrlFromNet: Inverter command reference status (0=command reference is not from network,
1=command reference is from network). Maps to inverter register 101 (operation mode status).
CtrlFromNet will be 1 whenever the operation mode status is a value of 0x0000 (NET mode), and will be
0 otherwise.
RefFromNet: Inverter speed reference status (0=speed reference is not from network, 1=speed
reference is from network). Maps to inverter register 101 (operation mode status). RefFromNet will be 1
whenever the operation mode status is a value of 0x0000 (NET mode), and will be 0 otherwise.
AtReference: Up-to-speed signal (0=not up-to-speed, 1=up-to-speed). Maps to inverter register 100
(status word), bit 3 (SU/up to frequency). Note that if the setting of inverter parameter Pr. 191 (SU
terminal function selection) is changed from its factory-default value, the indicated status of the
AtReference bit will no longer be accurate.