PROTOCOL-SPECIFIC INFORMATION
d) Under “Target Device”, set the “Data
Table Address” field to N12:1 (starting
target register=201) and set the
“MultiHop” field to Yes to cause the
“MultiHop” tab to appear.
e) Under the “MultiHop” tab settings, set
the “To Address” in the first row to the
inverter’s IP address, and the “To
Address” in the second row to 0. Refer
to Figure 71.
f) Close the dialog box. At this point, the
program should appear as shown in
Figure 72.
6) Assign a tag to the XIO element.
a) Double-click on the XIO element
located to the left of the MSG block.
Type in N20:0/15 (MSG instruction’s
enable bit). This configuration causes
the MSG instruction to automatically
retrigger itself when it completes.
While this is acceptable for the
purposes of this example, it can
produce high network utilization. In
Figure 71: MSG Configuration, "MultiHop" Tab
Figure 72: PLC Program after MSG Instruction
Configuration