EasyManua.ls Logo

Mitsubishi FX3U-4HSX-ADP - Maximum Number of Input;Output Points When CC-Link Master Is Used

Mitsubishi FX3U-4HSX-ADP
520 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
95
6 Examination of System Configuration
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
6.3.2 Maximum number of input/output points when CC-Link master is used
1. Calculation of maximum number of input/output points
When CC-Link master block is used, the following maximum number of input/output points can be connected.
*1. 224 points when the FX2N-16CCL-M is used.
The number of CC-Link points is calculated by the formula "32 points × number of stations" even when
remote I/O stations having less than 32 points are used.
For details, refer to the manual of the CC-Link master block used.
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output powered extension units/blocks and CC-Link remote I/O stations, the number
of input/output points and the total number of points are restricted.
Maximum number of
input/output points
384 points
Maximum number
of points
controllable on
system
Number of input/
output points
+
Total number of
input/output points
(A)(B)(C)(D)
Number of input/output
occupied points
(E) units
Number of points
occupied by special
function units/blocks
+
CC-Link remote I/O
(F) stations
Total number of points obtained by formula
"number of remote I/O stations
*1
(The number is multiplied by 32 points
32 points"
regardless of the number of remote I/O points.)
For details, refer to Subsection 6.3.1.
(A): Number of input/output points of main unit
(B): Number of input/output points of input/output
powered extension units
(C): Number of input/output points of input/output
extension blocks
(D): Number of remote I/O points of FX
2N
-64CL-M or FX
2N
-
16LNK-M
(E): Number of input/output points occupied by special
function units/blocks
(F): Number of remote I/O stations (units) connected to CC-
Link master
× 8
points
× 32
points
256
points
×
Special
function unit
FX
3U
-16CCL-M
Input
extension
block
X000 to X027
Y000 to Y027
Main unit
X030 to X057
Y030 to Y057
Input/output
powered
extension unit
X060 to X077
Input
extension
block
8 points
24/24
= 48 points
X100 to X117
CC-Link network
Remote I/O
(8 points)
Remote I/O
(16 points)
Remote I/O
(32 points)
Remote I/O
(32 points)
Remote I/O
(32 points)
Number of
remaining points
Number of input/output points (128 points)
0 points
384 points128 224 256160144
32 points × 5 units = 160 points
Number of
remaining points
Number of input/output points (excluding remote I/O points on CC-Link) + Number of
input/output occupied points
Up to 256 points
Number of input/output points occupied by special function units/blocks
Number of CC-Link input/output points
Up to 256 points
384 points or less in total
24/24
= 48 points
16/0
= 16 points
16/0
= 16 points
8 points

Table of Contents

Related product manuals