EasyManua.ls Logo

Mitsubishi FX3U-4HSX-ADP - Example of External Wiring (Source Input) [AC Power Supply Type]

Mitsubishi FX3U-4HSX-ADP
520 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
195
10 Input Wiring Procedures (Input Interruption and Pulse Catch)
10.2 24V DC Input Type (Common to Sink/Source Input)
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
10.2.5 Example of external wiring (source input) [AC Power Supply Type]
X0
S/S
0V
24V
Main unit
N
L
X1
X0
S/S
X1
Input extension block
X0
S/S
0V
24V
Input / output powered extension unit
N
L
X1
X0
S/S
X1
Input extension block
5V 0V 24V
5V 0V 24V
24+
Special function block
Fuse
5V 0V 24V
5V 0V 24V
5V 0V 24V
Class D
grounding
Input
impedance
Input
terminal
Input
terminal
Input
terminal
Three-
wire
sensor
Input
terminal
*1
*2
Two-wire
proximity
sensor
0V
24V
0V
24V
*1 Handle the power supply circuit correctly according to Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures."
*2 For an input device with a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3 In case of source input wiring, short-circuit the terminals of the extension units as well as the S/S terminal and the 0V terminal of
the
main unit.
*3
*3
Sink and source
input type
Sink and source input type
24-

Table of Contents