230
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
12 Output Wiring Procedures
This chapter explains the procedures for wiring the output terminals.
• Wiring procedures
• Procedures for cabling according to shape of output terminal
• Output wiring procedures
WIRING PRECAUTIONS
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or
extension units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 Ω or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm
2
or thicker.
Do not use common grounding with heavy electrical systems (refer to Section 9.4).
• Connect the AC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX
3U Series main unit and FX0N/FX2N/FX3U Series extension equipment in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U-4HSX-ADP and is the answer not in the manual?

Mitsubishi FX3U-4HSX-ADP Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U-4HSX-ADP
CategoryController
LanguageEnglish

Related product manuals