484
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
A Operation of Special Devices (M8000 -, D8000 -)
A-2 Special Data Register (D8000 to D8511)
High-Speed Counter Comparison, High-Speed Table, and Positioning
[D]8130
HSZ (FNC 55) instruction:
High-speed comparison table
counter
M8130
[D]8131
HSZ (FNC 55) and PLSY (FNC 57)
instructions:
Speed pattern table counter
M8132
[D]8132 Lower HSZ (FNC 55) and PLSY
(FNC 57) instructions:
Speed pattern frequency
M8132
[D]8133 Upper
[D]8134 Lower HSZ (FNC 55) and PLSY
(FNC 57) instructions:
Number of target pulses for
speed pattern
M8132
[D]8135 Upper
D 8136 Lower PLSY (FNC 57), PLSR
(FNC 59) instructions:
Accumulated total number
of pulses output to Y000
and Y001
D 8137 Upper
[D]8138
HSCT (FNC280) instruction:
Table count
D8138
[D]8139
HSCS (FNC 53), HSCR (FNC 54),
HSZ (FNC 55), and HSCT
(FNC280) instructions:
Number of instructions being
executed
D8139
D 8140 Lower
Accumulated number of
pulses output to Y000 for
PLSY (FNC 57) and PLSR
(FNC 59) instructions
D 8141 Upper
D 8142 Lower
Accumulated number of
pulses output to Y001 for
PLSY (FNC 57) and PLSR
(FNC 59) instructions
D 8143 Upper
[D]8144
Not used
D 8145
D 8146
D 8147
D 8148
[D]8149
Inverter Communication Function
D 8150
*1
Response wait time of inverter
communication [ch1]
[D]8151
Step number of instruction during
inverter communication [ch1]
Default: -1
M8151
[D]8152
*2
Error code for inverter
communication [ch1]
M8152
[D]8153
*2
Inverter communication error step
number latched [ch1]
Default: -1
M8153
[D]8154
*2
Parameter number when error
occurs during IVBWR (FNC274)
instruction [ch1]
Default: -1
M8154
Number and
name
Content of register
Correspond-
ing special
device
D 8155
*1
Response wait time of inverter
communication [ch2]
[D]8156
Step number of instruction during
inverter communication [ch2]
Default: -1
M8156
[D]8157
*2
Error code for inverter
communication [ch2]
M8157
[D]8158
*2
Inverter communication error step
number latched [ch2]
Default: -1
M8158
[D]8159
*2
Parameter number when error
occurs during IVBWR (FNC274)
instruction [ch2]
Default: -1
M8159
*1. Cleared when PLC power supply is turned from OFF to
ON.
*2. Cleared when PLC switches from STOP to RUN.
Advanced Function
[D]8160
Not used
[D]8161
[D]8162
[D]8163
D 8164
[D]8165
[D]8166
*3
Special block error condition
[D]8167
Not used
[D]8168
[D]8169
Access restriction status
*4
*3. Supported in Ver. 3.00 or later.
For details on the special block error condition, refer to
Subsection 14.6.4 Error Code List and Action.
*4. Access restriction status
*5. The accessibility is restricted depending on the keyword
setting status.
*6. "**" indicates areas used by the system.
Number and
name
Content of register
Correspond-
ing special
device
Present
value
Access restriction
status
Program
Monitor-
ing
Present
value
change
Read Write
H**00
*6
2nd keyword is not set.
*5
*5
*5
*5
H**10
*6
Write protection 
H**11
*6
Read / write protection 
H**12
*6
All online operation
protection
––
H**20
*6
Keyword cancel 

Table of Contents