PTS 400.3 PLUS Operation Manual_R02 Page 10/306
Advantages
• Two instruments in one compact case
• Two large 8.4” (640 x 480 pixels) colour TFT VGA displays with graphical user interface
• Data transfer and communication via 2 x USB (Type A and B) or 1 x ETHERNET
• Data storage on removable Compact Flash memory card
• Independent sets of UCT clamp-on CTs allow service, calibration or later purchase of clamp-on
CTs without factory return of the device.
Measurement Inputs
• 3 voltage inputs U1, U2, U3
• 3 direct current inputs I1, I2, I3
• 2 universal UCT clamp-on CT current inputs for I1, I2, I3
REFERENCE STANDARD - Functions
• Meter testing of pulse outputs (LED/disc mark/S0) and registers of active, reactive, apparent 1- or
3-phase, 3- or 4-wire energy meters with 3 pulse inputs and 3 pulse outputs
• Measurement of electrical parameters (UI , PQS, f, PF) including vector diagram, harmonic anal-
ysis and wave form display.
• Instrument transformer testing (CT/PT burden, CT/PT ratio)
POWER QUALITY ANALYZER - Functions
• Dips / Swells / Interruptions
• Harmonics / Interharmonics / Signal voltages
• Voltage unbalance
• Flicker
• Transient capture 100s (26.7 kHz)
Options
• Software CALegration
• GPS Time Synchronisation (integrated, order with instrument)
• Set of 3 UCT 120.3 clamp-on CT 120A (active error compensated)
• Set of 3 UCT 1000.3 clamp-on CT 1000A
• Set of 3 flexible UCT LEM.3 current probes FLEX 3000 (30/300/3000A)
• UCT AMP-LiteWire 3-phase adapter set for AmpLiteWire
• Primary current sensor AmpLiteWire 2000 A
• UCT VOLT-LiteWire 3-phase adapter set for VoltLiteWire
• Primary voltage sensor VoltLiteWire 40 kV
In order to meet these requirements, the PRS 600.3 offers the following main functions:
Simultaneous testing of up to three meters or registers of a multi-functional meter
Internal memory for measurement results and customer data
Vector diagram, harmonics spectrum, waveform and rotary field display for analysis of the mains
conditions
Active, reactive and apparent energy measurement in three-wire or four-wire circuits with inte-
grated error measurement and pulse output for energy
Voltage measurement
Current measurement, direct and with current transformer clamps up to 3000 A or hot sticks
Active, reactive and apparent power measurement per phase and sum of all phases
Phase angle, power factor and frequency measurement
Burden measurement and ratio test of PTs and CTs
Measuring of current, voltage and power transducers