EasyManua.ls Logo

MTE PTS 400.3 PLUS - Edit Load Point

Default Icon
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PTS 400.3 PLUS Operation Manual_R02 Page 85/306
7.2.1
Edit load point
Edit load point menu
This menu contains the following submenus and
functions:
Network selection menu
Edit voltage U or U1, U2, U3
Edit phase current I1, I2, I3
Edit phase angle current to voltage φ1, φ2, φ3
Phase sequence selection
Edit frequency
Network selection
Network selection menu
This menu contains the following func-
tions:
The predefined network types are
displayed
One Network Type can be selected
Select a network type.
Exit and accept selection, back to call-
ing menu.
Edit phase to neutral voltage U1, U2, U3
Changing only the setting of voltage U
1
will cause an automatic setting of U
2
and U
3
with
the set value of U
1.
The value for the phase to neutral voltage can be set between 0V...300V.
The voltage will be limited to <UmaxLN>.
The value for the phase to neutral voltage can be set in % of voltage Un.
The phase to neutral voltage will be limited to UmaxLN.
Edit voltage U
The voltage will be limited either to <UmaxLN> or <UmaxLL>.
The value for the voltage can be set between 0V...600V.
The value for the voltage can be set in % of voltage Un.
Warning!
The voltage U can be either the phase-phase voltage or the phase-neutral
voltage. See table Settings of voltage U depending on network type
[7.2.2]

Table of Contents