EasyManua.ls Logo

MTE PTS 400.3 PLUS - Page 229

Default Icon
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PTS 400.3 PLUS Operation Manual_R02 Page 229/306
3
Go to the setup of recording options [14.3]
Define the recording start options and the recording duration and time block configuration directly or
load predefined settings.
Example: Start at exact date and time, record 1 week in 1 block and then stop.
4
Setup of voltage and current inputs [14.4]
Select the current input (direct or type of clamp-on CT), which shall be used for I1, I2, I3 measure-
ment.
Manually select voltage and current ranges.
Note: The ranges will be fixed during recording. Therefore, the end of range values should be
higher than the max. reached voltage and current values during recording.
Setup and activate transformer factors for voltage and current transformers (optional)
Example: Direct voltage inputs used, internal voltage range 520V selected.
Note: The settings for the current inputs and current ranges do not matter for this example, because
only voltages are measured.
5
Check time and date
All recordings are saved with a time stamp with the actual date and time as in-
dicated in the status field in the lower right corner.
Check time and date settings and change if necessary at Data Base / Setup /
Clock setup [5.1].

Table of Contents