MultiSmart Installation & Operation Manual
15.1.3 Selecting Profiles Using a Timer
A timer can be used to set a specific date/time for a profile to be selected. Timer settings for each profile are
accessed through the advanced menu:
From the tree select: Pump Control
+ / -
Profile
+ / -
Select the desired profile from the list and press
+ / -
From the tree select: Timers
+ / -
Select the desired timer and press
+ / -
The following values can be set for each timer:
Enabled? (check the box to enable, uncheck to disable)
Period (Days) (The repeat period for the timer, 1-28 days)
Start date (only the date is actually used on this screen, the time is not used). This start date only
needs to be set if the timer is to be activated at some time in the future, or you want the timer to run
on a specific day each week (in which case you would set Period = 7)
Start time (this is the actual start time used by the timer)
Stop time
MultiSmart_IO_Manual_R20 Page 137 of 260