EasyManua.ls Logo

MultiTrode MultiSmart - Page 92

MultiTrode MultiSmart
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MultiSmart Installation & Operation Manual
Figure 96 - Pump and Level Alarm Delays
Use the arrows to select an alarm.
Enter new values, in seconds, using the keypad.
Push the Save button to commit the changes.
This screen changes the delays for all profiles.
12.4.1 Inter-pump delays
There are four different delays that operate between one pump stopping or starting and a second pump
starting or stopping.
Start-Start (10s default)
Stop-Stop (10s default)
Start-Stop (5s default)
Stop-Start (5s default)
12.4.2 Activation & Deactivation delays for individual pumps
An activation and deactivation delay is present for each pump.
Pump Activation Delay (0.5s default)
Pump Deactivation Delay (0.5s default)
12.4.3 Activation & Deactivation delays for level alarms
Each of the four level alarms have an activation delay (5s default) and a deactivation delay (10s default).
High-High Level
High Level
Low Level
Low-Low Level
NOTE:
Activation delays can be used to stagger equipment starts from a common level point.
Deactivation delays allow you to pump beyond the normal deactivation level for a set period of time.
NOTE: Activation delays can be used to prevent false alarm trips due to splashing or foam build-up, so
an alarm will only be raised if the level is above the alarm level for a certain time period. Deactivation
delays allow you to be sure the alarm condition has passed before clearing the alarm.
Page 92 of 260 MultiSmart_IO_Manual_R20

Table of Contents

Other manuals for MultiTrode MultiSmart