EasyManuals Logo

Omron CJ2 CPU UNIT SOFTWARE User Manual

Omron CJ2 CPU UNIT SOFTWARE
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #643 background imageLoading...
Page #643 background image
A-159
Appendices
CJ2 CPU Unit Software User’s Manual
A-3 Auxiliary Area
App
A-3-2 Read/Write Area (Set by User)
A729 to
A731
--- Power ON
Clock Data 4
These words contain the time at which the power was
turned ON three times before the startup time stored in
words A510 and A511.
A729.00 to A729.07: Seconds (00 to 59)
A729.08 to A729.15: Minutes (00 to 59)
A730.00 to A730.07: Hour (00 to 23)
A730.08 to A730.15: Day of month (01 to 31)
A731.00 to A731.07: Month (01 to 12)
A731.08 to A731.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
A732 to
A734
--- Power ON
Clock Data 5
These words contain the time at which the power was
turned ON four times before the startup time stored in
words A510 and A511.
A732.00 to A732.07: Seconds (00 to 59)
A732.08 to A732.15: Minutes (00 to 59)
A733.00 to A733.07: Hour (00 to 23)
A733.08 to A733.15: Day of month (01 to 31)
A734.00 to A734.07: Month (01 to 12)
A734.08 to A734.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
A735 to
A737
--- Power ON
Clock Data 6
These words contain the time at which the power was
turned ON five times before the startup time stored in
words A510 and A511.
A735.00 to A735.07: Seconds (00 to 59)
A735.08 to A735.15: Minutes (00 to 59)
A736.00 to A736.07: Hour (00 to 23)
A736.08 to A736.15: Day of month (01 to 31)
A737.00 to A737.07: Month (01 to 12)
A737.08 to A737.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
A738 to
A740
--- Power ON
Clock Data 7
These words contain the time at which the power was
turned ON six times before the startup time stored in
words A510 and A511.
A738.00 to A738.07: Seconds (00 to 59)
A738.08 to A738.15: Minutes (00 to 59)
A739.00 to A739.07: Hour (00 to 23)
A739.08 to A739.15: Day of month (01 to 31)
A740.00 to A740.07: Month (01 to 12)
A740.08 to A740.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
A741 to
A743
--- Power ON
Clock Data 8
These words contain the time at which the power was
turned ON seven times before the startup time stored in
words A510 and A511.
A741.00 to A741.07: Seconds (00 to 59)
A741.08 to A741.15: Minutes (00 to 59)
A742.00 to A742.07: Hour (00 to 23)
A742.08 to A742.15: Day of month (01 to 31)
A743.00 to A743.07: Month (01 to 12)
A743.08 to A743.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
A744 to
A746
--- Power ON
Clock Data 9
These words contain the time at which the power was
turned ON eight times before the startup time stored in
words A510 and A511.
A744.00 to A744.07: Seconds (00 to 59)
A744.08 to A744.15: Minutes (00 to 59)
A745.00 to A745.07: Hour (00 to 23)
A745.08 to A745.15: Day of month (01 to 31)
A746.00 to A746.07: Month (01 to 12)
A746.08 to A746.15: Year (00 to 99)
See Function col-
umn.
Retained Retained Written when
power is
turned ON.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write timing/
Related flags,
settings
Words Bits

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 CPU UNIT SOFTWARE and is the answer not in the manual?

Omron CJ2 CPU UNIT SOFTWARE Specifications

General IconGeneral
BrandOmron
ModelCJ2 CPU UNIT SOFTWARE
CategorySoftware
LanguageEnglish

Related product manuals