P071:1
st
speed runtime P075:5
th
speed runtime
P072:2
nd
speed runtime P076:6
th
speed runtime
P073:3
rd
speed runtime P077:7
th
speed runtime
P074:4
th
speed runtime P078:8
th
speed runtime
0.1(0.1 to 999.9)、1(1000 to 3600)Setting unit (s)
0000・0.1 to 6553 Data setting range (s)
In "P045: Multi speed function select", if setting value is 3 or 4, used to set 1
st
to 8
th
speed frequency
runtime.
Note
・ Each function is valid only when setting value is 3 or 4 in "P45: Multi speed function select".
・ When set to "0000", the inverter will not operate at the set speed. Timer's multi speed operation
will be applied only at speed whose time is set with P071~P072.
* "0000" is set to operate at the speed other than this speed.
P079:1
st
pulse input times P083:5
th
pulse input times
P080:2
nd
pulse input times P084:6
th
pulse input times
P081:3
rd
pulse input times P085:7
th
pulse input times
P082:4
th
pulse input times P086:8
th
pulse input times
Indication "0.1" = "one time" (Indication: 0.1 to 999.9)
Indication "1" = "ten times" (Indication: 1000 to 6553)
Setting unit (s)
0000・0.1 to 65530 Data setting range (s)
In "P045: multi speed function select", if setting value is 5 or 6, used to set pulse input times of 1
st
to 8
th
speed frequency.
Note
・ Each function is valid only when setting value is 5 or 6 in "P45: Multi speed function select".
・ When set to "0000", the inverter will not operate at the set speed. Pulse input multi speed
operation will be applied only at speed whose time is set with P079~P086.
* "0000" is set to operate at the speed other than this speed.
102
P045~P052
P061~P070
相关
参数
Related
parameters
相关
参数
P045~P052
P061~P070
Related
parameters