If only forward run operation is enabled, reverse run can be disabled to avoid the mishandling
of "reverse run operation".
If reverse run operation is set to be disabled, reverse run cannot be carried out during the
operation of panel, external control and communication.
Reverse run operation disabled (Only forward run
operation enabled)
1
Reverse run operation enabled (Both forward run
and reverse run operation enabled)
0
Details
Data setting
value
Note
P028Stop mode
Used to select whether to ramp-to-stop or coast-to-stop when stopping the inverter.
1
0
Data setting
value
The inverter output is shut off immediately by the stop signal.coast-to-stop
The frequency is decelerated by the stop signal according to
the deceleration time, and then the motor stops.
ramp-to-stop
DescriptionsDetails
P029Start frequency
Used to set the frequency which the inverter output starts when starting the inverter.
0.5 to 60.0
Data setting range (Hz)
P030Stop frequency
Used to set the frequency which the inverter output stops when the inverter deceleration to a stop.
0.5 to 60.0Data setting range (Hz)
P027Reverse run lock
79
P031P032
Related
parameters
P004
Related
parameters