Terminal mark Screw size
Tightening torque
N・m
Cable size
A,B,C M3
~
M2
0.5~0.6
0.25~0.75mm
2
(AWG24~AWG18)
0.22~0.25
0.25~0.75mm
2
(AWG24~AWG18)
■ Electric Cable Size and Control Circuit Terminal Tightening Torque
Wire's insulation
removing size
6mm
5mm
・Screwdriver: Small-size screwdriver
(Depth of the edge: 0.4mm/ Width of the edge: 2.5mm)
・Wire's insulation removing size
241
-
Common terminal of analog signals (⑬,⑭,⑯,⑰)
⑰
P124,125
P106-111
Second analog signal input terminal
Feedback signal input terminal controlled by PID
⑯
-
Common terminal of analog signals (⑬,⑭,⑯,⑰)⑮
P004
Frequency setting analog signal input terminal⑭
P090, P091Open-collector output terminal (E: Emitter)
⑫
P091Open-collector (TR2) output terminal (C2: Collector)
⑪
P097, 098
Multi-function analog signal output terminal ( 0~10V/PWM)
⑱
P004Frequency setting potentiometer connection terminal (+ 5V)
⑬
P090Open-collector (TR1) output terminal (C1: Collector)
⑩
-
Common terminal of input signals (②~⑧)
⑨
P040, P041
Multi-function control signal SW5 input terminal⑧
P039, P041
Multi-function control signal SW4 input terminal
⑦
P038, P041
Multi-function control signal SW3 input terminal
⑥
P037, P041
Multi-function control signal SW2 input terminal⑤
P036, P041Multi-function control signal SW1 input
④
P003Forward /reverse, reverse run signal input terminal
③
P003Start /stop, forward run signal input terminal
②
-
Common terminal of input signals (②~⑧)
①
Related Parameter
No.
Terminal Function
Terminal
No.
■ Explanation of Control Circuit Terminals
23