P042:JOG frequency
P043:JOG acceleration time
P044:JOG deceleration time
Used to set operation frequency, acceleration time and deceleration time during JOG operation.
[Parameter P042: JOG frequency]
[Parameter P043: JOG acceleration time]
[Parameter P044: JOG deceleration time]
・Run command select should be set to external control. (Value of parameter P003 is "2 to 5".)
・ SW function select should be set to JOG function.
・When SW set to JOG function is turned ON, the JOG operation preparation state is entered.
・JOG run/stop and forward run/reverse run are applied with terminals No.2 and 3.
・Meanwhile, refer to function descriptions on page 84.
・The display code for 0.04 s. is "0000".
0.1(0.1 to 999.9)、1(1000 to 3600)Setting unit (s)
0.04・0.1 to 3600Data setting range (s)
・The display code for 0.04 s. is "0000".
0.1(0.1 to 999.9)、1(1000 to 3600)
Setting unit (s)
0.04・0.1 to 3600
Data setting range (s)
0.5 to 400.0Data setting range (Hz)
Note
・JOG frequency under control of vector is 1Hz to 120Hz.
90