P016Electronic thermal select
P017Thermal current setting
Used to set the operation level of the electronic thermal when the motor overload is detected and
the inverter output is to be stopped.
Operation coasts to stop when OL is displayed.
0
Output frequency (Hz)
100
[Parameter P016 = 1]
Derating
(%)
50
0
Output frequency (Hz)
100
[Parameter P016 = 2]
Derating
(%)
50
90
60
25
0
Output frequency (Hz)
100
[Parameter P016 = 3]
Derating
(%)
50
60
15
Without output frequency deratingvalid
1
With output frequency deratingvalid
2
Forced ventilation motor specificationsvalid
3
OL trip will occur if a current that is 140% of the inverter's
rated current flows for one minute.
invalid
0
Details of function
Validity of
function
Data setting
value
*
Set these parameters according to the rated current
of applicable motor.
0.1 to 100.0Data setting range (A)
Example for setting current and thermal operation (P016 = 1)
Set current X 100% ⇒Does not operate
Set current X 125% ⇒operate (OL trip)
*
About derating
Function to automatically compensate operation level when motor cooling performance
drops during low-speed operation.
[Parameter P016: Electronic thermal select]
[Parameter P017: Thermal current setting]