P101:OV stop function select
When frequency setting signal is lower than data setting value, the inverter's output can be stopped
if the OV stop function is used effectively.
・ Setting data value "0000": OV stop function is not provided.
・ Setting data "0.5~400.0": OV stop function is provided. (OV stop frequency setting)
・When frequency setting signal is set with digits or communication, the inverter will not carry
out OV stop.
・When frequency setting signal is less than 1/100 (1%) full scale, command value will change
to 0Hz.
0000・0.5 to 400.0 Data setting range (Hz)
Note
・ If frequency setting signal is " analog setting (parameter P004 = "0","2","3","4","5","6") ", and
frequency setting value is below setting value of the OV stop function select, the inverter's
output will be stopped.
Max,5V,10V,20mA,
Output
frequency
0
Min,0V,0V, 4mA,
20mA
0mA
Frequency setting signal
100%
Setting
value
Run signal
Max. output frequency
[When P101 = 0.5~400]
AB
* A and B are in
OV stop state.
Lower
frequency clamp
・ If the OV stop function select is set to "0000", the inverter wil not carry out OV stop.
When frequency setting signal is less than 1/100 (1%) full scale, the inverter will continuously
run at the lower frequency limit.
[When P101 = 0000]
100%
[OV stop function]
111
P004, P099
P125
Related
parameters