P112:Skip frequency 1
P113:Skip frequency 2
P114:Skip frequency 3
P115:Skip frequency band width
If the load mechanism resonates at a specific inverter output frequency, a continuous operation
in that frequency band can be avoided by setting the skip frequency and the skip frequency band.
Skip frequency band width
(Parameter P115)
Skip frequency
(Parameters P112,113, 114)
Output
frequency
0
(Hz)
[Parameter P112: Skip frequency 1]
[Parameter P113: Skip frequency 2]
[Parameter P114: Skip frequency 3]
・Up to three skip frequencies can be set, and the skip frequency band can be set between 1
and 10Hz.
[Parameter P115: Skip frequency band width]
0000・0.5 to 400.0
Data setting range(Hz)
* "0000" is setting that the skip frequency is to be
disabled.
0・1 to 10
Data setting range(Hz)
* "000" is setting that the skip function is to be
disabled.