If an inverter fault trip occurs, the retry function will automatically reset the fault and will restart
(run) operation after the wait time has elapsed. Use this function to continue operation.
・Select the "retry function validity" and the details of the fault for carrying out retry with parameter P022.
・Set the "retry times" with parameter P023.
・The time interval for retrying is set with parameter "P026: Wait time".
・The fault warning signal will not be output during retry. If a fault occurs even when the set number
of retries has been carried out, a fault warning signal will be issued.
・If a fault not selected occurs during retry, a fault warning signal will be output, and the counted
retry times will be cleared.
・The counted retry times will be cleared when the power is turned OFF.
・If a fault dose not occur for 5 or more minutes, the counted retry times will be cleared.
[Parameter P022: Retry function]
[Parameter P023: Retry times]
P022:Retry function
P023:Retry times
When the retry function is used, the inverter may automatically start (restart).
Keep out of the machine.
(Secure personal safety before using this function.)
Failure to do so could lead to injury.
Execute retry only for overcurrent fault and heat sink fin abnormal overheating
(SC1/SC2/SC3/SC4/OC1/OC2/ OC3)
1
Execute retry only for overvoltage fault (OU1/OU2/OU3)2
Execute retry for overcurrent fault and heat sink fin abnormal heating (SC1/
SC2/SC3/SC4/OC1 /OC2/OC3)and overvoltage fault (OU1/OU2/OU3)
3
Retry function disabled (Retry is not carried out.)
0
Details
Data setting
value
1 to 10Data setting range(times)
75
Caution
!
P026
Related
parameters