Press the UP and DOWN button to select "CPY1".
(CPY1 after P151)
Press the MODE button.
[Continued from previous page]
Press the SET button.
(Current setting value is displayed.)
Press the UP button to set displayed value to "UPL".
Press the MODE button and enter the operation
preparation completed state.
Operation preparation
completed state
・・・
The normal stop state will be entered and the inverter
can be run.
(Operation status display mode)
Press the SET button to start the upload.
The upload indication will flicker.
→ When the upload ends, "End" will be displayed.
Note
・ When the upload ends, built-in memory parameter data and parameters of the main unit are the same.
・ If a run signal enters during uploading, the operation will not be activated. After the operation
preparation completed state is returned to, OP trip will occur.
・ While uploading the data, the set data will be written in non-volatile memory inside the inverter
and the data will be stored even if the power is turned off. Max. writing times of the non-volatile
memory inside the inverter is 100,000 times. Take note of the uploading times.
・ The function cannot be used during operation. Always use this function in the stopped state.
Press the SET button. (Increment in CPY2)
148
SET
SET
SET
MODE
MODE