Trips & Fault Finding 10-5
AC30 series Variable Speed Inverter
The drive has been configured to run in Closed Loop Vector control mode with a Pulse
Encoder IO Option, but the IO Option has not been correctly configured.
The drive has been configured to run in Closed Loop Vector control mode with a
System Board and/or a Pulse Encoder IO Option (using one of the 3 possible
encoder inputs), but the system board or the IO option has not been declared as
required.
An internal cooling fan has failed. This will reduce the lifetime of the power
electronics.
Return the power stack to a Parker Hannifin repair centre.
Current feedback phase missing
Check motor phase connections
A Power Loss Ride Through sequence has occurred and either
1650 Pwrl Time Limit
has been exceeded or the motor speed has reached a zero speed during the
sequence.
Encoder has failed whilst
operating in vector control of
induction motor. The drive
switches to sensorless
operation automatically (if this
feature is enabled), and
provides a warning to the
user.
Application trip 1. The application trips are controlled by the Application_Trips block in
the configuration. The text associated with each trip can be re-defined by the
Application_Trips_Text block in the configuration.