Compliance C-22
AC30 series Variable Speed Inverter
Internal Filter Disconnection
Disconnection of the EMC filter invalidates the CE EMC Declaration, the product becomes a component for incorporation and the
conformity of the complete equipment or installation becomes the responsibility of the installer.
There are separate disconnects for the internal overvoltage suppressors to earth (identified by the label ‘VDR’) and the internal filter capacitors to
earth (identified by the label ‘YCAP’).
DC supplied inverters do not have overvoltage suppressors to earth.
Frame D
To access the filter disconnect the top and bottom covers, as these need to be removed, then the Control Module, refer to Chapter 4 for removal
information. Remove the highlighted screws shown below.
The product should never be powered or operated without the covers, the EMC filter disconnect will
become live once the screw is removed.