Parameter Reference D-225
AC30 series Variable Speed Drive
PNO
Name
Path
Type
Default
Range
Units
WQ
View
Notes
MBus
1918
Preset Speed 2
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04363
1919
Preset Speed 3
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04365
1920
Preset Speed 4
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04367
1921
Preset Speed 5
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04369
1922
Preset Speed 6
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04371
1923
Preset Speed 7
Setup::Application::Preset Speeds
REAL
0.0
-100.0 to 100.0
%
ALWAYS
TECHNICIAN
5,8
04373
1924
Selected Preset
Monitor::Application::Preset Speeds
USINT
0 to 7
NEVER
TECHNICIAN
8
04375
1925
Preset Speed Output
Monitor::Application::Preset Speeds
REAL
-100.0 to 100.0
%
NEVER
TECHNICIAN
8
04377
1926
PID Setpoint Negate
Setup::Application::PID
BOOL
TRUE
ALWAYS
TECHNICIAN
5,8
04379
1927
PID Feedback Negate
Setup::Application::PID
BOOL
TRUE
ALWAYS
TECHNICIAN
5,8
04381
1928
PID Proportional Gain
Setup::Application::PID
REAL
1.0
ALWAYS
TECHNICIAN
5,8
04383
1929
PID Integral TC
Setup::Application::PID
TIME
1.00
0.01 to 100.00
s
ALWAYS
TECHNICIAN
5,8
04385
1930
PID Derivative TC
Setup::Application::PID
TIME
0.000
0.000 to 10.000
s
ALWAYS
TECHNICIAN
5,8
04387
1931
PID Output Filter TC
Setup::Application::PID
TIME
0.100
0.000 to 10.000
s
ALWAYS
TECHNICIAN
5,8
04389
1932
PID Output Pos Limit
Setup::Application::PID
REAL
100.00
0.00 to 105.00
%
ALWAYS
TECHNICIAN
5,8
04391
1933
PID Output Neg Limit
Setup::Application::PID
REAL
-100.00
-105.00 to 0.00
%
ALWAYS
TECHNICIAN
5,8
04393
1934
PID Output Scaling
Setup::Application::PID
REAL
1.000
-10.000 to 10.000
ALWAYS
TECHNICIAN
5,8
04395
1935
PID Output
Monitor::Application::PID
REAL
-105.00 to 105.00
%
NEVER
TECHNICIAN
8
04397
1936
PID Error
Monitor::Application::PID
REAL
-105.00 to 105.00
%
NEVER
TECHNICIAN
8
04399
1937
Disable Coast Stop
Setup::Application::Sequencing
BOOL
TRUE
ALWAYS
TECHNICIAN
8
04401
1938
Disable Quickstop
Setup::Application::Sequencing
BOOL
TRUE
ALWAYS
TECHNICIAN
8
04403
1939
Feedback On ANIN1
Setup::Application::Input Selection
BOOL
FALSE
ALWAYS
TECHNICIAN
8
04405