F-11 Technical Specifications
AC30 series Variable Speed Drive
Power Supply = 510V - 650V DC Average
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Product Code
Motor Power
Output Current
(A)
Input Current
(A)
Estimated
Efficiency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate %/kHz
(applied above nominal switching
frequency)
FRAME E: Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%
Normal Duty (Output Overload Motoring 110% for 60s)
34x-4E0016…
7.5kW
16
18
97%
4 / 16
5.5%
10Hp
14
15
34x-4E0023…
11kW
23
25
97%
4 / 16
5.1%
15Hp
21
22
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 3s short term rating)
34x-4E0016…
5.5kW
12
13
97%
4 / 16
4.9%
7.5Hp
11
12
34x-4E0023…
7.5kW
16
18
97%
4 / 16
4.9%
10Hp
14
16
FRAME F : Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%
Normal Duty (Output Overload Motoring 110% for 60s)
34x-4F0032…
15kW
32
35
97%
4 / 12
6.3%
20Hp
27
30
34x-4F0038…
18.5kW
38
41
97%
4 / 12
6.7%
25Hp
36
37
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 0.3s short term rating)
34x-4F0032…
11kW
23
27
97%
4 / 12
6.0%
15Hp
21
23
34x-4F0038…
15kW
32
35
97%
4 / 12
6.1%
20Hp
27
30