Wiring
Operating Manual PMCprotego D.48, PMCprotego D.72
1001735-EN-04
109
Please note the following important points under "Mains voltage", in the chapter entitled
"Function description":
} The mains voltage requirements (network configurations)
} The use of isolating transformers
Connector X0 Name Description
X0
PE L3L2L1
PE Earth conductor
L3 Mains voltage phase L3
L2 Mains voltage phase L2
L1 Mains voltage phase L1
Connector pin assignment
Mains voltage for power element Three-phase
L3
PMCprotego
X0
L1
L2
PE
L3
L1
L2
PE
F
N3
F
N1
F
N2
See Mains voltage [ 30]
L3
PMCprotego
X0
L1
L2
PE
L3
L1
L2
PE
F
N3
F
N1
F
N2
Use a line choke if the
mains voltage imbalance is
> 3% (type: 3L, u
k
= 2%)
The line choke (accessory)
should be insulated on the
mounting plate
Connection
Use the following fuses for F
N1
, F
N2
and F
N3
, depending on the device type.
Device type D.48 D.72 Type
Blow-out fuse orsimilar 60 A 80 A gRL or gL
400V/500V
(Fuse classes RK5/
CC/J/T, 600VAC
200kA, time-delay)