Wiring
Operating Manual PMCprotego D.48, PMCprotego D.72
1001735-EN-04
172
Output of SSI signals
Connector X5 Pin Designation Description
1 GND Ground
2 n.c. --
3 n.c. --
4 CLOCK Pulse signal
5 CLOCK\ Pulse signal inverted
6 DATA Channel B
7 DATA\ Channel B inverted
8 n.c. --
9 n.c. --
n.c.: Not connected
Connector pin assignment
Output circuit Output of SSI signals
6
7
4
Servo Drive
X5
PLC
5
CLOCK
CLOCK\
DATA
DATA\
GND
1
GND
CLOCK
CLOCK\
DATA
DATA\
R
T
R
T
Shield connection in the
connector
Always connect GND to the
earth on the control system
Select RT in accordance
with the cable impedance,
typically 150Ω