Saia-Burgess Controls AG
Manual Manual PCD 1 / PCD 2 Series │ Document 26 / 737 EN22 │ 2013-11-26
4
Communication interfaces
4-12
Onboard interfaces
4.5.7 Pro S-Net on PCD2.M480
The PCD2.M480 is equipped with a Pro S-Net interface as standard. This can be
used both for programming and for communication with other CPUs (that support
Pro S-Bus) and / or SBC RIOs.
Technical details:
Transmission rates up to 1.5 MBit / s
Number of stations up to 124 stations in segments of 32 stations each
Protocols
Profi S-Bus, Profi S-IO, DP Slave, HTTP in preparation
(multi-protocol operation on the same interface)
Connection diagram
Option
B1
S-Net
MPI
PCD2.M480
B2
B1
COM
PGU
Port #10 D-Sub
Pin
Probus DP
Master
S-Net
1 -
2 -
3 RxD / TxD-P
4 RTS / CNTR-P
5 GND
6 +5 V
7 -
8 RxD / TxD-N
9 -
For details of the configuration and programming of Profi S-Net functions, please
consult the specialised manuals.