Saia-Burgess Controls AG
Manual Manual PCD 1 / PCD 2 Series │ Document 26 / 737 EN22 │ 2013-11-26
5
Input/output (I/O) modules
5-31
Digital output modules, electrically isolated
5.5 Digital output modules, electrically isolated
PCD2.A200 4 make contacts 2 A, 250 VAC | 50 VDC
PCD2.A210 4 break contacts 2 A, 250 VAC | 50 VDC
PCD2.A220 6 make contacts 2 A, 250 VAC | 50 VDC
PCD2.A250 8 make contacts 2 A, 48 VAC | 50 VDC
pluggable 14-pole screw terminal block
PCD2.A410 8 digital outputs 0.5 A each, 5…32 VDC,
electrically isolated against PCD2 bus
Installation instructions
For reasons of safety it is not permissible to connect low voltages (up to 50 V) and
higher voltages (50 … 250 V) to the same module.
If a Saia PCD
®
 module is connected to a higher voltage (50 … 250 V), approved com-
ponents for this voltage must be used for all elements that are electrically connected
to the system.
Using higher voltage (50 … 250 V), all connections to the relay contacts must be 
connected on the same circuit, i.e. in such a way that they are all protected against
one AC phase by one common fuse. Each load circuit may also be protected
individually.
I/O modules and I/O terminal blocks may only be plugged in and removed when the
Saia PCD
®
and the external +24 V are disconnected from the power supply.
In the appendix, Chapter A.4 relay contacts, are calculation data and wiring sug-
gestions for the relay contacts. These data should be absolutely considered for safe
switching and a long life span of the relays.