EasyManuals Logo

SBC PCD1 Series User Manual

SBC PCD1 Series
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
Saia-Burgess Controls AG
Manual Manual PCD 1 / PCD 2 Series │ Document 26 / 737 EN22 │ 2013-11-26
CPUs and expansion housings
3-2
Generaltechnicaldetails
3
3.2 General technical details
Supply (external and internal)
Supply voltage
(accordingEN/IEC61131-2)
24 VDC -20 / +25% incl. 5% ripples
Power consumption
1)
PCD1andPCD2:typically625mA/15Wfor64I/Os
PCD2:typically833mA/20Wfor128I/Os
Capacity of internal
5 V bus
2)
PCD1: 750 mA
PCD2.M110/M120hardwareversion<H:1100mA
PCD2.M110/M120hardwareversion>=H:1600mA
PCD2.M150: 1600 mA
PCD2.M170: 1600 mA
PCD2.M480: 2000 mA
Capacity of internal +V bus
(16…24 V)
2)
PCD1: 100 mA
PCD2: 200 mA
Short voltage interruptions
(accordingEN/IEC61131-2)
)
≤10mswithinterval≥1s
1)Theloadsontheoutputsaregenerallymoresignicantforsizingthesupplythantheinternalpowerleakage
within the controller
2)WhenplanningPCD2systems,itisessentialtocheckthatthetwointernalsuppliesarenotoverloaded.This
check is especially important where analogue, counter and motion control modules are used, as these may con-
sume a lot of power.
Atmospheric conditions
Ambient
temperature
Mounting on vertical surface with vertically aligned connection
terminals:0 … +55°C
Inallothermountingpositions,areducedtemperaturerangeof
0 … +40°Capplies
Storage temperature -25 … +85°C
Relative humidity 30 … 95%withoutcondensation
Vibration resistance
Vibration accordingtoEN/IEC61131-2:
5 … 13.2Hzconstantamplitude1.42mm
13.2 … 150Hz,constantacceleration(simplegravitational
acceleration)
Electrical safety
Protection type IP20accordingtoEN60529
Air/leakage paths according to EN61131-2 and EN50178: between circuits and
bodies and between electrically isolated circuits: surge category
II,foulinglevel2
Test voltage 350V/50HzACfornominalunitvoltage24VDC
Electromagnetic compatibility
Electrostatic discharge according to EN61000-4-2: 8 kV: air discharge
8 kV: contact discharge
Electromagneticelds accordingtoEN61000-4-3: eldintensity10V/m,
80 … 1000MHz
Bursts according to EN61000-4-4: 4 kV on DC supply lines,
1/2kVonI/Osignallines,
1 kV on interface lines
Noise emission PCD1,
PCD2.M110/M120/M170
according to EN50 081-1: Class B (residential areas)