Using the Configurator
Microphone present Select this check box if there is a microphone connected
to this audio controller. If there are two or more
microphones, then one must be designated as the master
microphone and the Control enable required for mic
press to talk check box must be selected on every audio
controller with a microphone.
Master microphone Select this check box if you want the microphone
connected to this audio controller to be the master
microphone. If there are two or microphones, then one
(and only one) must be designated as master.
Control enable required for
mic press to talk
Select this check box if you want the operator to enable
the use of the microphone (through the menu or a switch).
This option must be selected if there is a microphone
connected to this node and there is at least one other
microphone on another audio controller.
Disable AGC Select this check box if you want to disable Automatic
Gain Control.
Pre-Tone Click the ... button to select which audio tone or digitized
message to use as the pre-tone. You can select the
standard, built in pre-tone, or you can select an existing
custom message, or you can create a new message.
Master Handset Select this check box if you want the telephone to be the
master handset. If you specify a master handset, the first
telephone line is used for that purpose. The line will be
hidden and cannot be used for anything else.
If line 0 is currently in use (either as a voice line serving
addressable phone modules, or as a conventional phone)
and you select this box you will be asked for confirmation
before the line is removed.
If you remove the master handset, line 0 will become
available. If there is a correlation from a telephone
selector switch to Call Control at this network node, you
will be asked for confirmation before the master handset
is removed.
Call-in Buzzer Select to enable the call in buzzer.
Control enable required for
master handset
Select this check box if you want the operator to enable
use of the master handset (through the Manual Control
Enable menu or a switch).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MMX Series and is the answer not in the manual?

Secutron MMX Series Specifications

General IconGeneral
BrandSecutron
ModelMMX Series
CategoryControl Panel
LanguageEnglish

Related product manuals